Ordering details | |
---|---|
Product type description | SRB100DR |
Article number | 101186279 |
EAN Code | 4250116202218 |
eCl@ss | 27-37-19-01 |
Approval | |
Approval | USA/CAN |
Classification | |
Standards | EN ISO 13849-1, IEC 61508, EN 60947-5-1 |
PFH value | ≤ 2,0 x 10-8/h (STOP 0) |
Mission time | 20 Years |
- notice | The PFH value is applicable for the combinations listed in the table for contact load (K) (current through enabling paths) and switching cycle number (n-op/y). In case of 365 operating days per year and a 24-hour operation, this results in the specified switching cycle times (t-cycle) for the relay contacts. Diverging applications on request. |
Global Properties | |
Permanent light | SRB100DR |
Standards | IEC/EN 60204-1, EN 60947-5-1, EN ISO 13849-1, IEC 61508 |
Compliance with the Directives (Y/N) | Yes |
Climatic stress | EN 60068-2-78 |
Mounting | snaps onto standard DIN rail to EN 60715 |
Terminal designations | IEC/EN 60947-1 |
Materials | |
- Material of the housings | Plastic, glass-fibre reinforced thermoplastic, ventilated |
- Material of the contacts | Ag-Ni, self-cleaning, positive action |
Weight | 250 |
Start conditions | Start button (monitored) |
Start input (Y/N) | Yes |
Feedback circuit (Y/N) | No |
Start-up test (Y/N) | No |
Reset after disconnection of supply voltage (Y/N) | Yes |
Automatic reset function (Y/N) | No |
Reset with edge detection (Y/N) | No |
Pull-in delay | |
- ON delay with reset button | 50 ms |
Mechanical data | |
Connection type | Screw connection |
Cable section | |
- Min. Cable section | 0,25 |
- Max. Cable section | 2.5 |
Pre-wired cable | rigid or flexible |
Tightening torque for the terminals | 0,6 |
Detachable terminals (Y/N) | No |
Mechanical life | 10.000.000 operations |
Electrical lifetime | Derating curve available on request |
restistance to shock | 30 g / 11 ms |
Resistance to vibration To EN 60068-2-6 | 10…55 HZ, Amplitude 0,35 mm, ± 15 % |
Ambient conditions | |
Ambient temperature | |
- Min. environmental temperature | −25 °C |
- Max. environmental temperature | +60 °C |
Storage and transport temperature | |
- Min. Storage and transport temperature | −40 °C |
- Max. Storage and transport temperature | +85 °C |
Protection class | |
- Protection class-Enclosure | IP40 |
- Protection class-Terminals | IP20 |
- Protection class-Clearance | IP54 |
Air clearances and creepage distances To IEC/EN 60664-1 | |
- Rated impulse withstand voltage Uimp | 4 kV |